Server Room Temperature and Network Closet Cooling: What Small Offices Get Wrong

Keep the air going into your equipment between 18 and 27 °C (about 64 to 81 °F), the range ASHRAE recommends. The bigger problem in small offices isn't the number; it's a closed closet with no way for heat to leave.

The recommended range

ASHRAE, the engineering society whose guidelines data centers follow, recommends an inlet air temperature of 18 to 27 °C (about 64 to 81 °F) for IT equipment. Inlet means the air entering the front of the equipment, not the temperature of the room by the door. Equipment can survive hotter conditions for a while, but heat shortens the life of power supplies, fans and batteries.

How much heat your equipment makes

Nearly every watt your equipment draws turns into heat. One watt equals about 3.41 BTU per hour, the unit air conditioners are rated in. So a closet drawing 1,000 watts produces roughly 3,410 BTU per hour of heat that has to go somewhere. Your UPS or PDU display shows the actual draw; add some headroom for growth.

What small offices get wrong

  • A closed closet with no ventilation. Heat builds up all day and peaks at night and on weekends, when the building turns off its air.
  • Relying on building air. Many NYC buildings shut down or reduce cooling after hours and on weekends. Your switches don't.
  • Blocking airflow. Equipment pulls air in the front and pushes it out the back. Boxes, cable bundles and a wall right behind the rack trap hot air.
  • Stacking equipment with no gaps or blanking panels, so hot exhaust gets pulled back into the front.
  • No temperature alerts. Nobody knows it's 35 °C in the closet until something fails.

Fixes, from cheapest up

  1. Clear the front and back of the rack and dress the cabling.
  2. Add a temperature sensor that sends alerts. Many UPS network cards and switches support this.
  3. Add a louvered door or an exhaust fan ducted out of the closet, if the building allows it.
  4. Install a dedicated cooling unit sized to the heat load, with its own power and a plan for condensate. In NYC buildings this often needs landlord approval.

Don't forget power

Cooling and power go together. A UPS keeps the network up through short outages, but if the cooling unit isn't on backup power, a long outage turns into a heat problem. Planning the closet as a whole is part of a proper network closet build.

Sources

Technical figures checked against the sources above. Standards and product details change; confirm with the manufacturer for your equipment.

FAQ

Frequently Asked Questions

ASHRAE recommends an inlet air temperature of 18 to 27 °C (about 64 to 81 °F) for IT equipment.

Add up the power draw of the equipment in watts and multiply by about 3.41 to get BTU per hour, then add headroom for growth.

Often not, because many buildings reduce or shut off cooling at night and on weekends while your equipment keeps running.

It's cheap and catches problems before equipment fails. Many UPS network cards and switches can send temperature alerts.

Keep Reading

More from our blog

Talk to an Engineer about your network closet

Hot closet, noisy fans or equipment that fails in summer? We'll check the heat load and fix the airflow.

Direct Lines

Call your local office

Each service area has its own direct line — your call goes straight to the team that covers your neighborhood.

NEW YORK
212-920-9466
Financial District, Midtown, SoHo
NEW YORK
917-268-4940
LIC, Astoria, Flushing
NEW YORK
917-268-4940
DUMBO, Williamsburg, Park Slope
NEW YORK
516-717-0404
Nassau & Suffolk counties
NEW JERSEY
201-374-0092
Bergen, Hudson, Essex
Insights

Related Articles

Certified Partners & Technology Stack

Cisco HP, Hewlett-Packard Microsoft